Automation task A water user shall be supplied with water on demand via four pumps. Four asynchronous motors drive one pump each. Assuming an output of 100% for each pump, an output of 400% is to be generated by cascading all four pumps. …
Automation task
A water user shall be supplied with water on demand via four pumps. Four asynchronous motors drive one pump each. Assuming an output of 100% for each pump, an output of 400% is to be generated by cascading all four pumps.
By switching pumps on and off an equal load for all pumps shall be ensured taking into consideration the operating times. The pumping output of a pump which has been released for maintenance shall be automatically taken over by a pump with free capacity.
Apart from the above described automatic operation, it shall also be possible to operate each pump manually.
In order to take into consideration the various pump types, it shall be possible to operate all pumps in positive and negative direction. The plant shall be operated via a monochrome Touch PanelAutomation solution
The 4 asynchronous motors are controlled with one SINAMICS G110 type frequency converter each.
In order to minimize the wiring expenses between the S7-1200 communication module CM 1241 and the frequency converter, the SINAMICS G110 with integrated bus interface (RS485 with USS protocol) was selected as a frequency converter. This allows control of all 4 frequency converters via S7-1200 CPU 1214C.
The compact controller S7-1200, CPU 1214C is configured via the programming user interface STEP 7 Basic V10.5, which enables theintegration of an USS library, included in delivery, for simple controlling of the frequency converter.